Technical Data
Max Continuous Operating Voltage | Ucpv | 1000VDC | 1500VDC |
Nominal discharge current(T2) | In | 20kA | 20kA |
Maximum dischargecurrent | Imax | 40kA | 40kA |
Maximum impact current(T1) | limp | 6.25kA | 6.25kA |
Protection level | Up | 3.5kV | 5.5kV |
Admissible short-circuit current | Iscpv | 100A | |
Icpv PV | 0.2 mA | ||
Connection mode | parallel | ||
Response Time | tA | 25ns | |
SPD Special disconnector | Recommend | SSD50X | |
Remote communication | With | ||
Remote communication connection | 1411:NO,1112:NC | ||
Remote contact rated current | 220V/0.5A |
Mechnical characteristics
Connection By screw terminals | 6-35mm |
Terminal Screw Torque | 2.5Nm |
Recommended Cable cross Section | ≥16mm² |
Insert wire length | 15mm |
Mounting DIN rail | 35mm(EN60715) |
Degree of Protection | IP20 |
Housing | PBT/PA |
Flame retardant grade | UL94VO |
Operating temperature | -40℃~+70℃ |
Operating relative humidity | 5%-95% |
Working atmospheric pressure | 70kPa~106kPa |