C7s series AC Contactor with novel appearance and compact structure is suitable for using starting & controlling the AC motor frequently. switching on and off the circuit at a long distance. It is used in combination with thermal relay to compose a magnetic motor starter.Standard: IEC 60947-1. IEC 60947-4-1.


Product Detail

Product Tags

Type C7s-09 C7s-12 C7s-18 C7s-25 C7s-32 C7s-38 C7s-40 C7s-50 C7s-65 C7s-80 C7s-95
Main circuit characteristic
Poles 3P
Rated insulation voltagelUi) V 690
Rated operating voltagelUe) V 380/400,660/690
Rated thermal current(lth),AC-1 20 20 32 40 50 50 60 80 80 125 125
Rated
operation
current(le)
AC-3,380/400V A 9 12 18 25 32 38 40 50 65 80 95
AC-3,660/690V A 6.6 8.9 12 18 22 22 34 39 42 49 49
AC-4,380/400V A 3.5 5 7.7 8.5 12 14 18.5 24 28 37 44
AC-4,660/690V A 1.5 2 3.8 4.4 7.5 8.9 9 12 14 17.3 21.3
Rated
operational
powerlPe)
AC-3,380/400V kW 4 5.5 7.5 11 15 18.5 18.5 22 30 37 45
AC-3,660/690V kW 5.5 7.5 10 15 18.5 18.5 30 33 37 45 45
AC-4,380/400V kW 1.5 2.2 3.3 4 5.4 5.5 7.5 11 15 18.5 22
AC-4,660/690V kW 1.1 1.5 3 3.7 5.5 6 7.5 10 11 15 18.5
Mechanical life 1200 1000 900 650
Electrical life AC-3 10000
times
110 90 65
AC-4 22 22 17 11 C7s-09~38
Frequency
of operation
AC-3 times/
hour
1200 600
AC-4 300 300
Connecting capability of main circuit terminal
Flexible wire 1 wire mm² 1…4 1.5…6 2.5…25 4…50
No terminal 2 wire mm² 1…4 1.5…6 2.5…16 4…25
Flexible wire 1 wire mm² 1…4 1…6 2.5…25 4…50
With terminals 2 wire mm² 1…2.5 1…4 2.5…10 4…16
Hard wire 1 wire mm² 1…4 1.5.…6   1.5.…10 2.5…25 4…50
No terminal 2 wire mm² 1…4 1.5… 2.5…10 4…25
Fastening torque N ·m 1.2 1.8 5 9
Coil
Rated control
voltagelUs)
50Hz V 24、36、48、110、127、220/230、240、380/400、415、440
50/60Hz V 24、36、48、110、127、220/230、240、380/400、415、440
Alowed control
circuit voltagelUs)
Operation V Installation inclination angle±22.5°:85%~110%Us;Installation inclination angle±5°:70%~120%
Release V Installation inclination angle±22.5°:20%~75%Us;Installation inclination angle±5°:20%~65%
Power
consumption
of coil
Actuation VA 60 70 200 200
Keep VA 6-9.5 6-9.5 15-20 15-20
Consumption W 1-3 1-3 6-10 6-10
Auxiliary contacts Type Amax Amax Bmax Cmax a d e
C7s-09.12.18 74.5 45.5 85.5 35 50/60
Auxiliary contacts specification A 11
C7s-25.32.38 83 56.5 97 40 50/70 - - -
Rated thermal current (ith) A 10
C7s-40.50,65 127.5 74.5 117 105 40 100/110 59
Rated operating
voltage(Ue)
AC V 380
C7s-80.95 127.5 85.5 125.5 105 40 100/110 67
DC V 220
Rated control
capacit
AC-15 VA 360
DC-13 W 33