Product Overview C7S series AC Contactor with novel appearance and compact structure is suitablefor using starting & controlling the AC motor frequently, switching on and off the circuit at a long distance. It is used in combination with thermal relay to compose a magnetic motor starter.
Standard: IEC60947-1, IEC60947-4-1.
Specifications
♦Rated operation current(le):9-95A;
♦Rated operation voltage(Ue):220V~690V;
♦Rated insulation voltage:690V;
♦Poles:3P;
♦Installation: Din rail and screw installation
Operating and Installation Conditions
Type |
Operating and Installation Conditions |
Installation category |
Ⅲ |
Pollution level |
3 |
Certification |
CE,CB,CCC,TUV |
Protection degree |
C7S-09~38:IP20;C7S-40~95:IP10 |
Ambient temperature |
limit of temperature:-35℃~+70℃,normal temperature:-5℃~+40℃, The average no more than +35C within 24 hours.If not in normal operating temperature range,please refer to”Instructions for abnormal environment” |
Altitude |
≤2000m |
Ambient temperature |
The maximum temperature of 70 degrees,the air relative humidity not exceed 50%,under lower temperature can allow for higher relative humidity.If the temperature is 20℃,the air relative humidity could up to 90%,Special measures should be taken for occasional condensation due to humidity changes. |
Installation position |
Inclination between installation surface and vertical surface should not exceed±5° |
Shock vibration |
Products should be installed and used without signicant shake,shockand wbration place. |