Contact Us

BY1-12.5-PV

BY1-12.5-PV

Short Description:

Location of  Use:String box,Inverter

Mode of  Protection:(DC+)-PE,(DC-)-PE,(DC+)-(DC-)

Surge Ratings:Itotal=up to 12.5 kA(10/350μs)     Itotal=up to 40 kA(8/20μs)

IEC/EN/UL Category:Class I+II/Type 1+2/Type 1CA

Protective Elements:High Energy MOV

Housing:Pluggable Design

 

Compliance:IEC61643-31:2018    EN 50539-11:2013+A1:2014    UL1449 4th Edition


Product Detail

Product Tags

BY1-12.5-PV  600 1000 1200 1500
IEC Electrical
Maximum Continuous Operating DC Voltage (DC+)-PE,(DC-)-PE UCPV 600V 1000V 1200V 1500V
(DC+)-(DC-) UCPV 600V 1000V 1200V 1500V
Nominal Discharge Current(8/20μs) In 20KA
Impulse Discharge Current(10/350μs) Iimp 6.25KA
Total Discharge Current(10/350μs) ITotal 12.5KA
Total Discharge Current(8/20μs) ITotal 40KA
Maximum Discharge Current(8/20μs) Imax 40KA
Voltage Protection Level (DC+)-PE. (DC-)-PE Up 2200V 4000V 4400V 5200V
(DC+)-(DC-) Up 2200V 4000V 4400V 5200V
Response Time tA <25ns
Short-Circuit Current Rating ISCPV 2000A
Number of Ports 1
UL Electrical
Maximum Permitted DC Voltage Vpvdc 600V 1000V 1200V 1500V
Voltage Protection Rating (DC+)-PE. (DC-)-PE VPR 1600V 2500V 3000V 4000V
(DC+)-(DC-) VPR 1600V 2500V 3000V 4000V
Nominal Discharge Current(8/20μs) In 25KA
Short-Circuit Current Rating SCCR 35KA 50KA 55KA 65KA

  • Previous:
  • Next:

  • Write your message here and send it to us