FN25-12D/T630-20 indoor AC high-voltage load switch Three-phase AC 50Hz. Indoor installation with rated voltage of 12KV. It is suitable for distribution and substation of industrial and mining enterprises, as the protection and control of electrical facilities, for dividing load current, closed-loop current, no-load transformer and cable charging current. FZRN25-12DmD-31.5 type indoor AC high-voltage vacuum load switch fuse combination is a three-phase AC 50Hz, rated voltage 12KV indoor device, suitable for industrial and mining enterprises distribution offices and substations and other fields. For load control and short circuit protection. Equipped with the ground switch, can withstand the short-circuit current, the operating mechanism can be manual and electric, cheaper to achieve the three remote control requirements of the power system. FZN25-12D, FZRN25-12D type load switches and combined electrical appliances are suitable for three-phase ring network or terminal power distribution stations and industrial electrical equipment, for load control and short circuit protection because the combination of electrical appliances for transformers and other electrical equipment protection than circuit breakers more reliable, more economical, especially suitable for ring network, double radiation power supply units and box-type substations.


Product Detail

Product Tags

00   Item              Data
FN25-12D/T630-20 FNRN25-12D/T125-31.5
1 Rated  voltage kV 12
2 Rated  frequency Hz 50
3 Rated Current A 630 1250
4 Rated insulation Level 1 min power frequency withstand voltage(RMS) kV 42-to-ground and white、ISolated off 48
Lightning  impulse  withstand  voltage(peak) 75-to-ground and white、isolated
5 Rated  dynamic  current(peak) kV 50
6 4s  thermal  current(A) kA 20
7 Rated active load breaking current kA 630
8 Rated  breaking  current A 630
9 Rated cable charging breaking current A 10
10 Rated  no-load  transformer  breaking  capacity A 1600
11 A 2000
12 r A SDLAJ-12 SFLAJ-1
13 Output energy of striker J 2-5
14 Rated short-circuit current kA 50     2-5(medium)
15 Rated dynamic thermal current of earth switch kA 50
16 Ground switch 2s heat stable current kA 20
17 current olEarn swi cn Auxiliary  circuit  voltage V AC110,220,DC110,220
18 Mechanicalife 1000