We know that we only thrive if we could guarantee our combined price tag competiveness and quality advantageous at the same time for Inverter , Spd Surge Protection Device , Black Mini Circuit Breaker , Good quality is factory' existence , Focus on customer' demand is the source of company survival and advancement, We adhere to honesty and superior faith working attitude, hunting forward towards your coming !
Good quality Solid State Safety Relay - Relay hw-RST 25 Phase Failure Under Overvoltage Sequence Relay – Hawai Detail:

Connection

The RST 25 can be connected as following in the installation diagram:
FlG1: Connection of the relay before operation.
When the relay is connected as in FIG 1, the three yellow LED’s L1,L2 and L3 light up when the power supply A1 phase L, the A2 Neutral, and the three phases”L1,”L2″and”L3″are properly connected.
If there is no under of overvoltage, phase failure of phase sequence, the green LED lights up,(terminals 11 and 14 are closed ) and the relay is ready for operation.
FIG2: Connection of the relay after operation.
When the relay is connected as in FIG 2,(the power supply Al phase L, the A2 Neutral are properly connected) after operation, the three phases”L1″,”L2″and”L3″are connected, andthere is no under of overvoltage, phase falure, phase sequence, the green LED lights up(terminals 11 and
14are closed) and the relay is ready for self retaining.
It is also possible to connect the power supply after operation in FIG2.
By both FIG’s 1 and 2, the terminal “PE”must be grounded.

Undervoltage
The desired undervoltage limit can be adjusted down to -25% UN.

Overvoltage
The desired overvoltage limit can be adjusted up to +25% UN.

Asymmetry
When adjusting over-and undervoltage limit, the asymmetric limit is also adjusted.

Time Delay
The switch off time can be adjusted by the potentiometer “Time’ Delay”from 0.1….5 seconds. With this function it is possible to adjust the time for the identification of the failure.

Contactor Control
If a phase fails during operation at load or one of the contacts of the contactor or circuit breaker is defect,(contact bounce or scorched contacts), RST 25 recognizes the failure, and also the feedback voltage, and switches off depending on the setting of “Time Delay”
The RST 25 controls the phase shift. If there is a phase failure during operation the angle from the feedback voltage is 30° and the RST 25 recognizes this failure.


Product detail pictures:

Good quality Solid State Safety Relay - Relay hw-RST 25 Phase Failure Under Overvoltage Sequence Relay – Hawai detail pictures


Related Product Guide:

Using a total scientific good quality management process, superior high quality and excellent faith, we get great name and occupied this field for Good quality Solid State Safety Relay - Relay hw-RST 25 Phase Failure Under Overvoltage Sequence Relay – Hawai , The product will supply to all over the world, such as: Vietnam, Oman, New Zealand, We adopted technique and quality system management, based on "customer orientated, reputation first, mutual benefit, develop with joint efforts", welcome friends to communicate and cooperate from all over the world.
  • With a positive attitude of "regard the market, regard the custom, regard the science", the company works actively to do research and development. Hope we have a future business relationships and achieving mutual success.
    5 Stars By Laura from Mongolia - 2017.10.25 15:53
    The company can think what our think, the urgency of urgency to act in the interests of our position, can be said this is a responsible company, we had a happy cooperation!
    5 Stars By Ethan McPherson from Tunisia - 2018.09.29 13:24
    Write your message here and send it to us