Product Detail
Product Tags
Shell frame grade current Inm (A) |
80 |
Rated current In(A) |
40,50,63,80 |
Rated operating voltage Ue |
AC230V |
Rated insulation voltage Ui |
AC400V |
Rated frequency (Hz) |
50 |
Rated impact withstand voltage Uimp (kV) |
4 |
Rated operating short-circuit breaking capacity Ics (kA) |
6 |
Rated remaining on and off capacity IΔn (kA) |
1.5 |
Rated residual current operating value lan IΔm (A) |
0.05-0.5 adjustable (can be turned off) |
Rated residual current non-operating value IΔno |
0.8ΙΔη |
Residual current operation delay time (ms) |
200-500 adjustable |
Limit non-driving time (s) |
At 21△n, it is 0.06s |
Instantaneous tripping type |
Type C |
Residual current operating characteristic type |
AC |
Loop current measurement range |
0-14ln |
Mechanical/electrical life (times) |
10000/4000 |
Protection level |
IP20 |
Installation method |
Standard rail installation |
Wiring ability |
maximum 35mm2 |