Contact Us

HWV6-80

Short Description:

Over-voltage    protection

Under-voltage     protection

Voltage  display(separate  ABC  phase  volt  measurement)

Three-phase  volt  unbalance  protection

Phase  sequence  protection(reverse  phase  protection)

Zero  line  break  protection

Phase  failure  protection

Over-voltage  protection  value  adjustable

Over-voltage  recovery  value  adjustable

Over-voltage  protection  action  time  adjustable

Under-voltageprotection   value   adjustable

Under-voltage  recovery  value  adjustable

Under-voltage  protection  action  time  adjustable

3  phases  volt  unbalance  protection  value  adjustable

3  phases volt  unbalance  protection action time adjustable

Delay  time  after  power-on  adjustable

Fault  recovery  delay  time  adjustable

Reset  mode  selection

Fault   inquiry

Factory  data  reset


Product Detail

Product Tags

Technical Parameters

Rated voltage 3 phase 4 wires 230V/400VAC50/60Hz
 

Rated current

1-80AAdjustable(default 80A)

1-63AAdjustable(default 63A)

1-50AAdjustable(default 50A)

Over-voltage protection value range 221V-300V-OFF Adjustable(default 280V)
Over-voltage recovery value range 220V-299V(default 250V)
Over-voltage protection action time 0.1-10 second (default 0.2s)
Under-voltage protection value range 219V-150V-OFF Adjustable(default 160V)
Under-voltage recovery value range 151V-220V(default 180V)
Under-voltage protection action time 0.1-10 second(default 0.2s)
3 phases volt unbalance protection value 10%-50%-OFF(default 20%)
3 phases volt unbalance protection action time 0.1-10 second (default 1s)
Delay time after power-on 2-255 second (default 2s)
Failure recovery delay time 2-512 second(default 60s)
Display model LCD
Faulty Signal Character
Grounding system TT,TN-S,TN-C-S
Installation DIN rail
Working environment Temperature:-20℃~+50℃ Humidity:<85%

Altitude:≤2000 m