Standard
|
IEC1008, GB16916, BS EN61008
|
Rated voltage (ln)
|
230V AC 400V AC
|
Rated current (ln)
|
25, 40, 63 (A)
|
Rated residual operating current
|
30, 100, 300,500mA
|
Rated residual non-operating current
|
0.5
|
Rated current off-time
|
≤0.1s |
Minmum value of rated making and breaking
capacity (lm)
|
1KA
|
Rated conditional short-circuit current (lnc)
|
In=25, 40A InC=1500A
In=63A InC=3000A
|
Endurance: on load
|
200 cycles
|
Off load
|
2000 cycles
|
Standard
|
|
Tripping time
|
Undelayed
|
Min. 10ms delay
|
|
Min. 40ms delay
|
|
With selective disconnecting function
|
|
Rated voltage
|
230/400V
|
Rated tripping current
|
10, 30, 100, 300, 500mA
|
Sensitivity
|
AC and pulstating DC
|
Rated short
|
10kA with 63Agl back-up fuse
|
Circuit strength
|
63kA with 80A gl (F7-80 and 863)
|
6kA (rated current 63A) with 63A g
|
|
Maxinmum back-up fuse for
|
63A gl
|
Short circuit protection
|
80A gl (F7-80 and-863)
|
Maxinmum back-up fuse for
|
45A gl (F7-25 and-40A)
|
Oveload protection
|
40A gl (F7-80A)
|
Desistance to climatic conditions
|
Accordong to IEC 1008
|
Degree of protection
|
Built-in switch IP40
|
Endurance electrical comp.
|
≤4.000 operating cycles |
Mech comp.
|
≥20.000 operating cycles
|