RCCB 16A 40A 63A 1P+N 3P+N 6KA Din rail AC A B type residual current circuit breaker RCCB

Short Description:

Product Advantages

Operating mechanism is plastic structure, operating performance is more stable and reliable than metal structure. such as release force, mechanical life cycle. For environmental protection is better than metal type and also the type is new generation mechanism.

Inside all current-carrying parts: copper.

All screws are with the plastic cover seal the holes, It’s move safety can not open the products in easy.

A Big sizes transparent signboard can help user makesome special marks in the signboard area.


Product Detail

Product Tags

Technical Data

Rated current:16A,20A,25A,32A,40A,50A,63A

Rated voltage:230V~1P+N,400V~3P+N

Rated frequency:50/60Hz

Number of pole:2Pole

Module size:36mm

Circuit type:AC type,A type, B type

Breaking capacity:6000A

Rated residual operating current:10,30, 100,300mA

Optimum operating temperature:-5℃ to 40

Terminal Tightening torque:2.5~4N/m

Terminal Capacity(top): 25mm2

Terminal Capacity(bottom):25mm2

Electro-mechanical endurance:4000 cycles

Mounting:35mm DinRail

The very new tripping structure make more safety

Suitable Busbar:PIN Busbar

Compliance

IEC61008-1

IEC61008-2-1