SSD 50X/80/160

Short Description:

At  present,the  front  end  of  the  lightning  protection  device  is  mainly  equipped

with  a  small  plastic-case  circuit  breaker  or  fuse, and  is  not  equipped  with  SPD

Specific  Disconnector,when  lightning  strikes,due  to  the  structural  limitations  of

the  circuit  breaker, resulting  in  lightning  residual  voltage  is  very  large,it  is  easy

to  damage the  back-end  equipment,and  easy to  cause  circuit  breaker trip.The  other

case,the  rated  frequency  current  of  the  circuit  breaker  is  very  large,and  trip  current

far  exceeds  the  rated  current, Power  frequency   continuous  flow   can’t  cut  off,easy  to

cause  fire,then   it   is  necessary  to  be  equipped  with   the  SPD  Specific Disconnector

to  solve  the  above  problem


Product Detail

Product Tags

Technical Data

Model number SSD50X SSD80 SSD160
Max Continuous Operating Voltage (AC)Uc 440V 440V 440V
Maximum non-trip discharge current Imax / 80kA 160kA
Maximum non-trip impact current limp 30kA / /
Response Time tA 100ns
Power frequency current trip value It It 3A
Residual current-Leakage current at lpe NONE
Admissible short-circuit current Isccr

25000A

Mechnical characteristics

Connection Byscrew terminals 6-35mm²
Terminal Screw Torque 39.9 Ibf-in 4.5 Nm
Recommended Cable cross Section ≥16mm²
Mounting DIN rail 35mm(EN60715)
Degree of Protection IP20
Housing PBT/PA G20 VO anti-fire
Operating temperature -40℃~+70℃
Operating relative humidity 5%-95%
Working atmospheric pressure 70kPa106kPa