Contact Us

T1 X15/X30/X50

T1 X15/X30/X50

Short Description:

It is mainly used to provide T1 protection for various electronic and electrical 

equipment in buildings vulnerable to lightning overvoltage.Mainly used as 

primary protection equipment in the main distribution system.


Product Detail

Product Tags

Technical Data

Max Continuous Operating Voltage (AC)Uc 275V 320V 385V 440V
Rated Voltage (AC)Un 220V 220V 220V 220V
Maximum impact current(Type 1) limp 15/30/50kA 15/30/50kA 15/30/50kA 15/30/50kA
Protection level Up(L-N) 2.5kV 2.5kV 2.5kV 2.5kV
Protection level Up(N-PE) 2.5kV 2.5kV 2.5kV 2.5kV
Follow Current Interrupt Rating ln 50kA
Response Time tA 100ns
SPD Special disconnector Recommend SSD50X
TOV N-PE 1200V
Residual current-Leakage current at lpe NONE
Admissible short-circuit current Isccr 50000A
Remote communication No

Mechnical characteristics

Connection By screw terminals 6-35  mm²
Terminal Screw Torque 2.5Nm
Recommended Cable cross Section ≥16mm²
Insert wire length 15mm
Mounting DIN rail 35mm  (EN60715)
Degree of Protection IP20
Housing PBT/PA
Flame retardant grade UL94VO
Operating temperature -40℃~+70℃
Operating relative humidity 5%-95%
Working atmospheric pressure 70kPa106kPa

 

 


  • Previous:
  • Next:

  • Write your message here and send it to us