Contact Us

T2 60/80/100/160

T2 60/80/100/160

Short Description:

lt  is  mainly  used  to  provide  T2  protection  for  various  electronic  and electrical

equipment  in  buidings  vulnerable  to  lightning  overvoltage. Mainly used as

primary protection equipment in the main distribution system.


Product Detail

Product Tags

Technical Data

Model number 60 80 100 160
Max Continuous Operating Voltage Uc(V~) 385/440 385/440 385/440 385/440
Nominal discharge current(8/20μs) In(kA) 30 40 60 100
Maximum discharge current(8/20μs) Imax(kA) 60 80 100 160
Protection level Up(kV) <2.2/2.5 <2.5/3.0 <2.5/3.0 <2.5/3.0
Response time (ns) <25 <25 <25 <25

General parameter

Access wire area (mm²) ≥10 ≥16 ≥16 ≥16
Access ground cross-sectional area (mm²) ≥16 ≥16 ≥16 ≥16
SPD Special disconnector Recommend SSD 60 SSD 80 SSD 100 SSD 160
Working environment 40~+70°C,relative humidity<95%(below 25℃)
Remote communication connection 1411:NO,1112:NC

Mechnical characteristics

Connection By screw terminals 6-25mm²
Terminal Screw Torque 2.5Nm
Recommended Cable cross Section ≥16mm²
Insert wire length 15mm
Mounting DIN rail 35mm(EN60715)
Degree of Protection IP20
Housing PBT/PA
Flame retardant grade UL94VO
Operating temperature 40℃~+70℃
Operating relative humidity 5%-95%
Working atmospheric pressure 70kPa106kPa