SPD 40KA lightning arrester surge protection device

Short Description:

Suitable range

TU2 SPD is generally parallel connected onto the front circuit of the required protected circuit equipment, as close as possible the down circuit terminal. The SPDis connected with one end of the circuit conductor(phase line L or neutral line N), and the other end of the connecting line of equipment grounding device, for the lightning equipotential connection.


Product Detail

Product Tags

Model

Protection zone

Protection level

Suitable location

TU2-10
TU2-20

LPZ1,LPZ2 zone boundaries of and LPZn
zone

 Class 3

Normally installed in the distribution box of the premises; or installed in the computer information equipment, electronic equipment and control equipment, or the nearest lighting box, socket box.

TU2-40
TU2-60

boundaries of LPZ0B and LPZ1 zone,or LPZ1 and LPZ2 zone

 Class2

Usually installed in the building distribution electric box,metering box;or installed in the computer center,motor housing,building control room,monitoring room, industrial automation,operation room and other places of power distribution box;also can be installed in the general distributionbox of the six floors below building, or the general distribution box of villa

TU2-80
TU2-100

LPZOA,LPZ0B zone boundaries of LPZ1 zone

 Class1

Usually installed in the piercing
lined low voltage main distribution
cabinet

TU2-1

Used in LPZ0A,LPZ0B zone

 Class 1

Usually used in lightning riskhigher equipment system of the first primary surge protection, installed in the general distribution box of distribution box, outdoor distribution box and so on.

Distribution network grounding systemvoltage

Grounding system

TT system

TN-S system

TN-C-Ssystem

IT system

The maximum voltage of the grid

345V/360V

253V/264V

253V/264V

398V/415V

Main technical parameters and performance

Project Name

Parameter

TU2-10

TU2-20

Nominal discharge current

 In(kA)

   5

   10

Maximum discharge current

 Imax(KA)

10

20

Maximum continuous operating voltage

 Uc(V)

 275

320

 385

 275

320

 385

Voltage protection level

 Up(kV)

 1.0

1.3

1.3

 1.3

1.5

1.5

Test classification

   Grade III testing

   Grade III testing

Poles

   2,4,1N

   2,4,1N

Structure type

   D,B type

    D,B type

operation status

 Window indicator

Colorless or green:normal,red: fault

Colorless or green:normal,red: fault

Backup protective
appliances(suggestion)

 Backup fuse

   gl/gG16A

     gl/gG16A

 Backup CB

   C10

   C16

 dimensions

   Refer to drawing no.1,3,4

    Refer to drawing no.1,3,4

 

Project Name

Parameter

TU2-10

TU2-20

Nominal discharge current

 In(kA)

 20

30

Maximum discharge current

 Imax(KA)

40

60

Maximum continuous operating voltage

 Uc(V)

 275

320

 385

420

 275

320

 385

420

Voltage protection level

 Up(kV)

 1.5

1.5

1.8

2.0

 1.8

2.0

2.2

2.2

Test classification

   Grade III testing

   Grade III testing

Poles

   1,2,3,4,1N,3N

 1,2,3,4,1N,3N

Structure type

   D,B,X type

    D,B,X type

operation status

 Window indicator

Colorless or green:normal,red: fault

Colorless or green:normal,red: fault

Backup protective
appliances(suggestion)

 Backup fuse

   gl/gG40A

     gl/gG60A

 Backup CB

   C32

   C50

 dimensions

   Refer to drawing no.1,3,4

    Refer to drawing no.1,3,4