Contact Us

X15RE/B+C

X15RE/B+C

Short Description:

The surge protection device belongs to T1+T2 AC power surge protector,which is

installed between the power supply network and the equipment to drain,suppress

and reduce the overcurrent and overvoltage caused by induced lightning strikes or

the power grid system,so as to reduce the harm to the electrical equipment.The

product is equipped with built-in thermal release device and fuse,fuse can be

replaced.It is mainly used for lightning protection of rail transit power system.


Product Detail

Product Tags

Technical Data

Max Continuous Operating Voltage (AC)Uc 275V 385V
Rated  Voltage (AC)Un 220V 220V
Maximum  impact  current(T1) limp 12.5 kA 12.5 kA
Nominal discharge current(T2) In 20kA 20kA
Maximum discharge current Imax 40kA 40kA
Protection level Up 2.0kV 2.0kV
Follow Current Interrupt Rating   300A 300A
Response Time tA 25ns 25ns
SPD Special disconnector Recommend SSD50X SSD50X
TOV N-PE 1200V 1200V
Residual current-Leakage current at lpe NONE NONE
Remote communication With With
Remote communication connection 1411:NO,1112:NC
Remote contact rated current 220V/0.5A

Mechnical characteristics

Connection Byscrew terminals 6-35mm²
Terminal Screw Torque 2.0 Nm
Recommended Cable cross Section ≥10mm²
Insert wire length 15mm
Mounting DIN rail 35mm(EN60715)
Degree of Protection IP20
Housing PBT/PA
Flame retardant grade UL94VO
Operating temperature -40℃~+70℃
Operating relative humidity 5%-95%
Working atmospheric pressure 70kPa106kPa