YUANKY HWM32RT thermal magnetic adjustable circuit breaker 2P 3P 4P 160A 320A 630A 800A power distribution motor protection MCCB

Short Description:

Outline

HWM32RT series circuit breaker is the company combining with the advantages of the international similarproducts at home and abroad and the demand of the market research and development level of the new version of the breaker.

This breaker’s rated in sulation volage is 690V, is applied to distribution network circuit of AC 50HZ, rated working voltage up to 690V, rated working current up to 800A, which is for electricenergy distribution, circuit protection, protecting power supply facility from destroying by the foult of overloading, short circuit and undervoltage ,meanwhile it is also used for protection from unfrequent starting, over loading, short circuit and unervdtage of the eletromotor.

This breaker has such characteristics of company volume, high short circuit interrupting capacty, shortflach arcing and etc which is a ideal product for users,This breaker can be installed vertically(upright),and also horizontally.

This breaker comply with standard IEC60947-2GB 14048.2.


Product Detail

Product Tags

Product Features

Miniaturization design

Product volume miniatu rization, such as the size of the same size of the original 125 shell shelf 63 sheu, can meet the customer’s personality needs of the product installation size

Size uniform

The same shell level, different sub ability(CSMH)different functions (air,leakage )product installation size is completely consistent

The function of the reasonable parameter setting

Circuit breaker can realize long-time delay overload inwerse time, short circuit instantaneous action protection functions such as paramets setting, users can set their own protective properties required,the distribution network is used in the circuit breaker on the lower levet with more reasonable.

Suitable working environment and installation condition

Altitude less than 2000m

Ambient medium temperature is from -50 Cto+40C(+45C for shipping product)

Can withstand moist cuir

Can with stand mold

Can withstand nuclear radiation

Max incination is 22.5°

It can still work reliably if the product subjects to the normal vibration from ships

It can still work reliably if the product subjects to the earthquake(4g)

Put in the place where is no explosion danger and conductive dust, cant corrode metel and destroy the insnlation sleet.

Put in the place where is no sleet.

 

Selection Guide

HWM32  RT  -  160  H  Z  /  3  300  2  A  Q1  D  Q  2

Type The adjustable type Frame Inm Breaking capacity Icu/Ics(KA)
HWM32 RT 160 H
MCCB RT: Therm-mag

T/A:Therm/mag

160,320,630,800

Remark:

160 Frame upgrade from 125

320 Frame upgrade from 250

630 Frame upgrade from 400

 

160

320

630

800

C

15/7.5

30/15

35/18

S

35/25

35/25

 

M

50/35

50/35

50/35

50/35

H

70/50

70/50

70/50

70/50

Operation Poles Tripping mode and inner accessary Rated current(A)
P 4 300 160
P:Motor-driven

Z:Rotory handle

W:Direct

Motor-driven operation

DC1, DC2, DC3

2:2P

3:3P

4:4P

First figure means tripping unit way

2:Only with magnetic release

3:Thermal release+magnetic release body

Remark:

The last two figures means accessory code

(see accessaries list)

160

 

 

320

 

 

630

 

 

800

20-25, 25-32, 32-40, 40-50,

50-63, 63-80, 80-100,

100-125, 125-160

100-125, 125-160,

160-200, 200-250,

250-320

200-250, 250-320,

320-400, 400-500,

500-630

500-630, 630-800

Application Option for 4P MCCB
2 A
1:Power distribution

2:Motor-protection

A:N pole without protection, ON/OFF without

B:N pole without protection, ON/OFF switched

Accessary Voltage Motor-driven operation voltage Connection Connection plate
Q1 D1 Q 2
UVT

Q1:AC220V

Q2:AC240V

Q3:AC380V

Q4:AC415V

Shunt

F1:AC220V

F2:AC380V

F3:DC110V

F4:DC24V

Auxiliary

J1:AC125V

J2:AC250V

J3:DC125V

J4:DC24V

DC1

D1:AC220V

D2:AC230V

D3:AC380V

D4:AC400V

DC3

D5:AC230V

D6:AC110V

D7:DC220

D8:DC110

D9:AC110-240V

D10:DC100-220V

Q:Front

H:Rear

C:Plug-in

1:W/O

2:W

Remark: DC1, DC3 motor-driven operating voltage see extenal accessaries table.