YUANKY S7-125 MCB 10KA 240V 415V 80A 100A 125A mini circuit breaker MCB 1P 2P 3P 4P

Short Description:

Technical Data

Rated current (In)

80A,100A,125A

Poles

1P  2P  3P  4P

Rated voltage (Ue)

1P:240/415V~

2/3/4P:415V~

Insulation voltage (Ui)

500V

Rated frequency

50/60Hz

Rated breaking capacity (Icn)

10KA

Rated operating short circuit breaking capacity (Ics)

7.5KA

Tripping curve

C  D

Electrical and mechanical life

20000


Product Detail

Product Tags

MCB-1

Overload Current Protection Characteristics

Rated Current (A)

Test Procedure

Test Current

Initial State

Tripping or Non-tripping Time Limit

Expected Result

Remark

80A

100A

125A

A

1.05In

cold

t≤2h

No tripping

B

1.3In

After test A

t≤2h

tripping

The current steadly rises to the specified value within 5s

C

2.55In

cold

1s<t<120s

tripping

D

8In

cold

t0.2s

No tripping

Turn on the auxiliary switch to close the current

12In

t<0.2s

Installation

Contact position indicator Yes
Protection degree IP20
Reference temperature for setting of thermal element 30
Ambient temperature -5~+40and its average over a period of 24h does not exceed +35
Terminal connection type Cable/Pin -type busbar
Storage temperature -25~+70
Terminal size top/bottom for cable 50mm2
Tightening torque 2.5N.m
Mounting On din rail FN 60715 (35mm) by means of fast clip device
Connection Top and bottom

Combination with accessories

Auxillary contact YES
Alarm contact YES
Shunt release YES
Under voltage release YES

MCB-6


  • Previous:
  • Next:

  • Write your message here and send it to us